1. Scope of the standard
DSTU IEC 60947-6-1 concerns transfer switching equipment for low-voltage systems. In standby power applications, ATS systems are built around these devices: they disconnect the load from one source and connect it to another.
The standard applies to equipment for systems where the load supply may be interrupted during transfer. The typical application range extends to 1000 V AC or 1500 V DC.
For a customer, this has a straightforward implication: an ATS must be assessed by more than its current rating in amperes. Equipment class, utilisation category, short-circuit withstand capability, transfer logic and mechanical interlocking all matter.
2. Key terms
The standard uses the term transfer switching equipment. This equipment contains one or more switching devices and is intended to transfer a load between power sources.
| Abbreviation | Meaning | Practical relevance to an ATS |
|---|---|---|
| TSE | Transfer switching equipment. | The general term for power switching equipment that transfers a load between sources. |
| MTSE | Manually operated transfer switching equipment. | An operator performs the transfer manually. This is not a fully automatic ATS. |
| RTSE | Remotely operated transfer switching equipment. | The transfer command is issued remotely, while the control logic may be external. |
| ATSE | Automatic transfer switching equipment. | The closest equivalent to the familiar engineering concept of an ATS: the sources are monitored automatically. |
3. How automatic transfer works
Automatic transfer switching equipment monitors the normal source parameters. If these move outside permissible limits, the load is transferred to an alternative source. Once the normal source is restored, the system can transfer the load back.
Transfer may take place immediately or after a time delay. The arrangement may also include an off position where required by the facility operating logic.
A failure to transfer is not the only hazard in an ATS. An unintended connection between sources is much more serious. Interlocking is therefore a fundamental safety requirement, not an optional addition.
4. Classes PC, CB and CC
One of the most useful sections of the standard for practical ATS selection classifies equipment by its short-circuit performance.
| Class | Meaning | Engineering conclusion |
|---|---|---|
| PC | Equipment capable of making and withstanding short-circuit currents, but not intended to break them. | A typical class for dedicated ATS switching devices. External short-circuit protection is required. |
| CB | Equipment with overcurrent releases that can break short-circuit currents. | Based on circuit breakers. Provides protection, but has different operating mechanisms and transfer speeds. |
| CC | Contactor-based equipment capable of making and withstanding short-circuit currents, but not intended to break them. | Not suitable for every critical ATS application. Endurance, interlocking and utilisation category require careful verification. |
5. Utilisation categories AC-31, AC-32 and AC-33
The utilisation category indicates the type of load for which the device is intended. This is critical for an ATS: switching a predominantly resistive load is very different from switching motors, transformers, compressors, ventilation equipment and mixed loads.
| Category | Typical load | ATS selection guidance |
|---|---|---|
| AC-31A / AC-31B | Non-inductive or slightly inductive loads. | The lightest duty. It should not be assumed suitable for industrial facilities without analysis. |
| AC-32A / AC-32B | Mixed resistive and inductive loads, including moderate overloads. | Closer to real building services systems, but often insufficient for critical facilities. |
| AC-33A / AC-33B | Electric motors or mixed loads containing motors, resistive loads and some lighting. | One of the key categories for industrial and critical-duty ATS equipment. This is where a makeshift circuit-breaker arrangement is clearly out of its depth. |
6. Which characteristics must be checked?
The standard addresses more than rated current. Correct selection requires assessment of a complete set of parameters.
Power circuit parameters
Rated operational voltage, current, frequency, number of poles, type of current and operating sequence.
Switching capacity
Making and breaking capacities, utilisation category, cycle endurance and load conditions.
Short circuit
Short-circuit making capacity, conditional short-circuit current, short-time withstand current and coordination with protective devices.
Product designation
The nameplate must state the manufacturer, type or serial number, the ATS compliance standard—DSTU IEC 60947-6-1 / IEC 60947-6-1—Class PC / CB / CC, voltage, current, frequency and utilisation category.
7. Construction and interlocking requirements
The operating mechanism must prevent simultaneous connection of the load to the normal and alternative sources. This must hold under all conditions, not only when everything is in working order and the doors are closed.
For Class PC/CC equipment, the mechanism must ensure that transfer is completed so that the load circuit does not remain permanently disconnected unless required by the operating logic. Class CB equipment may include a disconnected position or an intentional delay, depending on its construction.
The practical conclusion is that the power switching mechanism, interlocking, controls and indication in a high-quality ATS must form a single system. Simply placing two devices side by side does not create a safe ATS.
8. Testing and acceptance
The standard describes typical test sequences: verification of construction, functioning, operational performance, temperature rise, dielectric strength, short-circuit withstand capability and electromagnetic compatibility.
Acceptance of new equipment requires more than the presence of a data sheet. The operating mechanism, settings, transfer sequence, operating thresholds and insulation dielectric strength must be checked.
9. Practical conclusion
DSTU IEC 60947-6-1 is useful because it moves the discussion of ATS equipment beyond a cabinet with controls to specific transfer switching equipment characteristics: class, utilisation category, endurance, interlocking, marking, testing and actual ability to operate with the load.
For critical facilities, the right question is not simply how many amperes, but which equipment class and utilisation category apply, what redundancy arrangement is used, how interlocking is implemented and whether the characteristics are verified by testing.