STAVR
Control, monitoring and communications

ASCO Group 5 controller in STAVR Series 7000 ATS

In STAVR Series 7000 ATS, the ASCO Group 5 controller monitors the power sources and controls the power transfer switch. The optional Power Meter adds electrical measurements.

The Group 5 controller, optional Power Meter and optional 72EE2 / ASCO 5170 QEM module form the control and monitoring system. The specific functions are determined by the ATS configuration and technical specification.

More about ASCO-based STAVR Series 7000 ATS and LV switchboards.

ASCO controller and Power Meter in STAVR Series 7000 ATS
The ASCO controller manages transfer, while the optional Power Meter measures the electrical parameters of the supply and load.
Multilingualcontroller user interface
Configuration-dependentTransfer time is confirmed for the specific switch configuration
99 events — Group 5 controller logfor operation and analysis
Optional 72EE2 / ASCO 5170 QEM moduleEthernet, RS-485, Modbus TCP/IP or RTU and SNMP, depending on the configuration
Operating logic

Transfer according to source status

The controller does more than command the operating mechanism. It checks permissives, power switch position, priorities and interlocks.

01

In-Phase Monitor — Feature 27

This function is available on the relevant 7ATS/7ATB configurations with Feature 27 (In-Phase Monitor) and delays the command until the relative phase angle between the sources is acceptable.

02

Phase sequence monitoring

Three-phase monitoring checks the phase sequence of the normal and standby sources; the reference sequence is defined in the settings.

03

Source voltage monitoring

Upper and lower voltage thresholds are set separately for the normal and standby sources. Values outside the set limits are taken into account by the transfer logic.

04

Preferred source

Automatic transfer with selection of a preferred source and configurable retransfer after that source recovers.

05

No source priority

Equal-priority source operation without automatic retransfer when the previous source recovers.

06

Source acceptability monitoring

The controller evaluates source voltage, frequency and phase conditions and permits transfer only when the set conditions are met.

07

Stand-alone source protection

Overload monitoring with provision for disconnecting non-priority circuits or the entire load according to the configured operating sequence and ATS equipment.

08

Manual mode

Forced source selection or movement of the power transfer switch to the open centre position.

09

Settings protection

A password protects operating parameters from unauthorised or accidental changes.

10

Transfer time delays

Configurable delays for responding to source failure, transferring to the standby supply and retransferring after the normal supply recovers. The delays prevent transfer in response to brief voltage dips.

Electrical parameters

Source and load measurements

The controller uses source parameters for ATS logic, while the optional ASCO Power Meter extends supply and load measurements for operation and monitoring.

Power sources

Two three-phase incoming supplies: voltage, frequency and phase conditions of each source.
Source comparison: voltage difference ΔU, frequency difference Δf and phase-angle difference Δφ.
Phase monitoring: phase loss and reverse phase sequence.
Operating time: duration of supply from each source and continuous system operation.
Optional measurement
Power Meter
Optional ASCO Power Meter panel

The ASCO Power Meter measures electrical quantities and makes them available on the local display and through a serial interface. THD is measured by the Power Meter, not by the ATS controller.

Optional ASCO Power Meter measurements
U

Voltage

Phase-to-neutral and phase-to-phase voltages, and their average values.

I

Current

Current in each phase, neutral conductor current and average current.

P

Power

Active power in kW, reactive power in kVAR and apparent power in kVA, per phase and total; power factor PF.

E

Energy

Imported, exported and net energy in kWh; leading, lagging and total reactive energy in kVARh; total apparent energy in kVAh.

Hz

Frequency, voltage THD and current THD

Supply frequency, total harmonic distortion of voltage (THD U) and current (THD I). These parameters are measured by the optional Power Meter, not by the ATS controller.

MAX

Maximum demand

Maximum power demand in kW for hourly, daily, monthly, annual and other periods, referenced to the real-time clock.

Operating data

Event log and diagnostics

After a fault, the sequence of states and the parameters preceding transfer provide the evidence needed for analysis.

Group 5 controller 99-event log

The real-time clock records the date, time, operating mode changes, fault conditions and transfer commands.

  • cause of transfer to standby;
  • recovery of the normal source;
  • alarm and service messages;
  • operator actions in manual mode.

Status and alarm messages

The controller displays the current source and power switch status, active warnings and the reasons for operating mode changes.

  • availability of the normal and standby sources;
  • actual power transfer switch position;
  • active alarm messages;
  • local and remote access to events through the communications system.
Standby sources

Generator control

The start sequence is coordinated with the ATS circuit, generator readiness, time delays and load retransfer conditions.

Generator set

Generator set start and stop

The controller issues the emergency generator start command and manages the retransfer sequence after the normal source recovers.

⏱

Seven Group 5 generator exercise programmes

The start time, day of the week, week of the month and running duration are set for each programme.

kW

On-load or off-load

A test run can transfer the load to the emergency source or run the generator without transferring the load.

Configuration and integration

Local and remote communications

Optional 72EE2 / ASCO 5170 QEM module: Ethernet, RS-485, Modbus TCP/IP or RTU and SNMP, depending on the configuration. The ASCO Group 5 controller and optional Power Meter connect to the 72EE2 / ASCO 5170 QEM module, which forwards the data to the supervisory system.

Optional communications: Group 5 + optional Power Meter → 72EE2 / ASCO 5170 QEM → supervisory system
CTRL

ASCO controller

Sends source status, switch position, commands and alarm messages to the 72EE2 / ASCO 5170 QEM.

PM

ASCO Power Meter

Sends measured electrical quantities for the supply and load to the 72EE2 / ASCO 5170 QEM.

72E

Optional 72EE2 / ASCO 5170 QEM interface module

Combines controller and Power Meter data and prepares it for transmission to an external system.

NET

Ethernet, RS-485, Modbus TCP/IP / RTU and SNMP

The 72EE2 / ASCO 5170 QEM transmits data using the selected interface and protocol, depending on the configuration.

Mechanical transfer time
50–150 msDepends on the power transfer switch construction.
Technical clarification

The controller defines the transition sequence

The actual transfer time is determined by the power switch mechanism configuration.

0 ms means no interruption to the power supply, not zero mechanism operating time. In CTTS, brief parallel overlap is permitted only after the source synchronism conditions have been met.

Need a specific STAVR Series 7000 operating sequence?

Controller selection requires the source arrangement, power switch type, rated current, generator operating sequence, signal list and supervisory monitoring requirements.