STAVR logo
Industrial ATS · ASCO platform

STAVR Series 7000

Complete ATS and LV switchboards with ATS based on ASCO Series 7000 automatic transfer switches.
Power switching, control, protection, indication and auxiliary equipment are designed as a complete assembly for the specific power supply arrangement.

STAVR · ASCO SERIES 7000STAVR Series 7000 LV switchboard
STAVR Series 7000 LV switchboard with bypass
STAVR Series 7000 LV switchboard with the cabinet open
ASCOautomatic power transfer platform
2 / 3sources in typical project configurations
3P / 4Pversions to suit the neutral arrangement
Open / CTTStransition type depends on the version and specification
Series configurations

The same STAVR engineering approach — based on ASCO Series 7000 switches

Series 7000 is used in complete ATS assemblies, LV switchboards with ATS, multiple-source systems and no-break transfer configurations. The cabinet equipment is defined by the single-line diagram and the facility’s requirements.

Open STAVR LV switchboard with two 400 A ASCO ATS units2×400 A

Two-source ATS

Utility–utility or utility–generator. Source parameter monitoring, mechanical interlocking and a project-specific retransfer sequence.

ATS page
Open 1600 A STAVR ATS cabinet based on ASCO Series 70001600 A

1600 A ATS

A complete high-current ATS: ASCO Series 7000 power transfer switch, busbars, controller, protection, indication and auxiliary circuits in a metal cabinet.

ATS page
STAVR Series 7000 LV switchboard — two 800 A sections2×800 A

LV switchboards with ATS

Incoming supply, standby supply, bus sectioning, distribution, protection, metering and control in a coordinated system of metal cabinets.

Complete LV switchboards
Open ASCO CTTS 800 A cabinet forming part of a complete STAVR assemblyCTTS 800 A

No-break ATS

Brief contact overlap is permitted only when the differences in source voltage, frequency and phase angle are within acceptable limits.

No-break transfer
The photographs show examples of STAVR equipment from the catalogue. The specific switching mechanism, controller, current rating and cabinet design are defined by the technical specification.
Single-line arrangements

The series defines the platform; the circuit defines system operation

The number of sources, power contact positions, neutral switching, permissives and interlocks must be clearly defined in the design documentation.

Typical utility–utility–generator three-source ATS arrangement with two ASCO controllers

Typical utility–utility–generator architecture: two coordinated ATS units, power switch position monitoring and a generator start/stop command.

No-break ATS transfer sequence

No-break transfer: the controller does not synchronise the sources; it waits until the phase-angle, frequency and voltage differences fall within the set limits. Brief contact overlap is then permitted.

Power switching section

ASCO Series 7000 switching mechanism

This is the principal difference from STAVR Series WN.

The switch, operating mechanism, power contacts, mechanical interlocks and auxiliary contacts form a single functional assembly. STAVR adds the controller, protection, indication, terminal circuits, metal cabinet and other equipment required by the design.

01
Mechanical interlockingMechanically prevents an impermissible connection between sources in normal operation.
02
3P or 4P versionsNeutral switching is determined by the earthing arrangement and protection requirements.
03
Position monitoringAuxiliary contacts confirm the actual power switch position for automatic control and supervisory monitoring.
04
Service configurationManual operation, bypass or isolation is provided where required by the operating conditions.
3000 A ASCO Series 7000 automatic transfer switch mechanism in a STAVR cabinet3000 A

An actual 3000 A ASCO Series 7000 power transfer switch installed in a cabinet. The number of poles and operating mechanism configuration are specified for each project.

Actual configurations

Power switching assembly, bypass and service access

These photographs show actual equipment assemblies rather than promotional mock-ups. The construction and component arrangement vary with the current rating, circuit and maintenance requirements.

Actual ASCO mechanism with the cover removed and power contacts exposed

Mechanism with the cover removed

The power contacts, operating mechanism and mechanical linkages are visible. The photograph retains the full working assembly so that construction details remain visible.

ASCO Series 7000 Bypass-Isolation in an open STAVR cabinet

Bypass-Isolation

A configuration with bypass and isolation of the power transfer switch for maintenance while supplying a critical load.

STAVR three-source 3 × 400 A LV switchboard with ASCO Series 7000 devices3×400 A

Three-source LV switchboard, 3 × 400 A

A three-source LV switchboard with 400 A ASCO Series 7000 devices. The transfer arrangement and source priorities are defined by the technical specification.

Transition modes

The transfer method is determined by the load characteristics

The correct operating sequence cannot be selected from the rated current alone. The permissible interruption, motors, UPS, variable frequency drives and process requirements must all be considered.

Open transitionOne source is disconnected before the other is connected. Transfer time is up to 50 ms. The ATS has no maintained intermediate position, so it cannot remain between its two operating positions.
Delayed transition through the off positionA delay is set between disconnecting one source and connecting the other. The controls monitor phase loss and source overload and can immediately disconnect a faulty incoming supply.
No-break transferOnly in the appropriate CTTS configuration: brief contact overlap after checking that the differences in source parameters are within acceptable limits.
Preliminary selection

Parameters are confirmed for the specific circuit

The previous catalogue covers several ASCO series, so its general figures have not been automatically carried over to the Series 7000 page.

Rated voltageSource operating voltage and frequency, control circuits and control power supply.
Design currentRated load current, overloads and the standby source operating duty.
Short-circuit currentsThe withstand capability of the power switching assembly and coordination with protective devices are verified by calculation.
Number of poles3P or 4P, taking account of the neutral arrangement, earthing and protection.
Number of sourcesTwo, three or a special configuration with a coordinated transfer sequence.
Transition typeOpen transition, delayed transition through the off position or CTTS, according to load requirements.
Metal cabinetDegree of protection, environmental rating, mounting method and cable entry arrangement.
Service and bypassManual operation, bypass circuit, isolation and maintenance access as specified.
ASCO controller and Ethernet/RS-485 interface module in a STAVR cabinet

ASCO controller and installed Ethernet / RS‑485 interface module. The available interfaces and protocols are confirmed for the specific equipment configuration.

OptionASCO Power Meter measurement module for the ATS controller

ASCO Power Meter is an optional module for measuring voltage, current, frequency, active, reactive and apparent power, power factor and other electrical parameters.

Control and monitoring

The controller is selected to suit the operating sequence

The controller must support the number of sources, transition method, generator set requirements, measurements, event log and supervisory monitoring. A single model is not assigned to the entire series without defining the equipment configuration.

Source monitoring: voltage, frequency, phase sequence and phase loss, depending on the configuration.
Time delays: failure confirmation, generator start, transfer, retransfer and cool-down.
Generator control: start/stop, testing, prime/standby operation or duty rotation, according to the circuit arrangement.
Transition modes: checking permissives, positions and source parameters before issuing a command.
Measurements and event log: the available data depends on the controller; the optional ASCO Power Meter extends the range of measured electrical quantities.
Integration: volt-free contacts, serial or network interfaces, according to the selected configuration.
Additional features

The equipment configuration is defined by the technical specification

The switching mechanism is the core of an ATS, but the reliability of the complete system also depends on protection, control, installation, measurement and ease of maintenance.

01

Metering and measurement

Energy meters, multifunction meters, current transformers and test circuits.

02

Manual bypass

A bypass circuit for ATS servicing without prolonged interruption to the critical load.

03

SPD

Surge protection with correctly coordinated protective devices and PE/N connections.

04

Alarm indication

Switch position, source availability, alarms and overall system status.

05

Supervisory monitoring

Transmission of status, measurements and events to SCADA/BMS, according to the controller’s capabilities.

06

Load management

Shedding or staged connection of non-priority load groups when operating from a source with limited capacity.

07

Neutral switching

3P or 4P configuration to suit the earthing arrangement, protection and standby source.

08

Special control logic

Coordination with two generators, bus-section switching devices, UPS, BESS or process control systems.

i

Draft note before publication

Four items need to be confirmed for the current Series 7000 specifically: rated current range, current controller models, available communication protocols and the current product designation structure. The page can then be added to the navigation and indexing.

i

The catalogue defines the platform but does not replace engineering design

The final ATS configuration is determined by the design current, short-circuit currents, load characteristics, number of sources, neutral arrangement and continuity requirements. See also DSTU EN 60947-6-1 and the article on neutral switching.

Need STAVR Series 7000 for a specific circuit?

Send a single-line diagram or the basic parameters: current, voltage, sources, number of incoming supplies and poles, transition type, bypass, protection and supervisory monitoring requirements.