STAVR
Control, monitoring and communications

Controller in STAVR ATS

The controller monitors the power sources, implements the transfer sequence, controls generators, records events and sends data to the supervisory system.

The specific controller model is defined by the technical specification. The functions depend on the ATS circuit, number of sources, power switch type and monitoring requirements.

Examples of industrial controllers in STAVR ATS assemblies
Examples of controllers with different functional capabilities. The controller is an integral part of the complete assembly, not simply an accessory on the cabinet door.
Ukrainianuser interface language
50–100 mstotal time for fast-transfer configurations
200 eventslog for operation and analysis
USB · RS-485 · Ethernetlocal configuration, Modbus RTU and TCP/IP
Operating logic

Transfer according to source status

The controller does more than command the operating mechanism. It checks permissives, power switch position, priorities and interlocks.

01

Fast in-phase transfer

Fast transfer takes place only under in-phase conditions. The controller checks the voltage, frequency and phase-angle differences between the sources and determines when a command to the operating mechanism is permitted.

02

Phase rotation monitoring

The controller checks the phase sequence of the normal and standby sources and inhibits transfer if the phase rotation is incorrect.

03

Source voltage monitoring

Upper and lower voltage thresholds are set separately for the normal and standby sources. Values outside the set limits are taken into account by the transfer logic.

04

Preferred source

Automatic transfer with selection of a preferred source and configurable retransfer after that source recovers.

05

No source priority

Equal-priority source operation without automatic retransfer when the previous source recovers.

06

Load protection

The controller prevents the load from being supplied by a source whose parameters are outside the set limits and performs transfer or disconnection according to the configured sequence.

07

Stand-alone source protection

Overload monitoring with provision for disconnecting non-priority circuits or the entire load according to the configured operating sequence and ATS equipment.

08

Manual mode

Forced source selection or movement of the power transfer switch to the open centre position.

09

Settings protection

A password protects operating parameters from unauthorised or accidental changes.

10

Transfer time delays

Configurable delays for responding to source failure, transferring to the standby supply and retransferring after the normal supply recovers. The delays prevent transfer in response to brief voltage dips.

Electrical parameters

Source and load measurements

Parameters are displayed per phase and used both for ATS logic and operational monitoring.

Power sources

Two three-phase incoming supplies: voltage, frequency and phase conditions of each source.
Source comparison: voltage difference ΔU, frequency difference Δf and phase-angle difference Δφ.
Phase monitoring: phase loss and reverse phase sequence.
Operating time: duration of supply from each source and continuous system operation.
Power quality
THD U / THD I

Measurement of total harmonic distortion of voltage (THD U) and current (THD I), and display of individual harmonics from the 3rd to the 21st order, with the appropriate controller configuration.

U

Load voltage

Per-phase voltage monitoring at the output of the complete ATS assembly.

I

Load current

Per-phase measurement through current transformers.

P

Power

Active power P, reactive power Q, apparent power S and power factor cos φ.

Operating data

Event log and diagnostics

After a fault, the sequence of states and the parameters preceding transfer provide the evidence needed for analysis.

200-event log

The real-time clock records the date, time, operating mode changes, fault conditions and transfer commands.

  • cause of transfer to standby;
  • recovery of the normal source;
  • alarm and service messages;
  • operator actions in manual mode.

Black-box recording function

The controller can store five data sets for transfer events for detailed analysis.

  • parameters for the 50 seconds before the event;
  • parameters for the 10 seconds after the event;
  • analysis of source and load conditions;
  • investigation of abnormal transfer behaviour.
Standby sources

Generator control

The start sequence is coordinated with the ATS circuit, generator readiness, time delays and load retransfer conditions.

1–2

One or two generators

Start and stop control of one or two generators according to the selected circuit arrangement. Two-generator systems can implement duty rotation or a prime/standby arrangement.

⏱

Scheduled start

Daily, weekly or monthly generator test runs.

kW

Testing

Scheduled on-load or off-load generator runs, where provided for in the design.

Configuration and integration

Local and remote communications

The interfaces provide access to parameters, measurements and the event log without intervention in the ATS power switching section.

USB

Local configuration

On-site commissioning, parameter changes and software updates.

485

Isolated RS-485

Galvanically isolated port for communication using Modbus RTU.

LAN

Ethernet 10/100 Mbit/s

Remote data exchange using Modbus TCP/IP and integration with the supervisory system.

I/O

Programmable outputs

Output contacts can operate in pulsed or maintained mode.

50–100 msTotal fast-transfer time for the relevant configurations
Technical clarification

The time depends on the power switch

The total time includes controller response and mechanical operation of the power transfer switch. The actual value depends on the rated current, construction and mass of the moving parts: high-current devices take longer to transfer.

0 ms is not the mechanism operating time. It can only describe the absence of a supply interruption during no-break transfer with synchronised sources and brief contact overlap.

Need a specific ATS operating sequence?

Controller selection requires the source arrangement, power switch type, rated current, generator operating sequence, signal list and supervisory monitoring requirements.